EasyManua.ls Logo

Siemens OXYMAT 64 - Configuring; Configuration Submenu; Analog Output (Function 70)

Siemens OXYMAT 64
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
5.4 Operating functions
OXYMAT 64
Operating Instructions, 06/2008, A5E00880383-03
81
5.4.6 Configuring
5.4.6.1 Configuration submenu
Configuration O
2
7O Analog outputs
71 Relay outputs
72 Binary inputs
73 ELAN - Configuration
...continue
Figure 5-46 Configuration submenu
All functions of this menu are only accessible via the code of level 2.
This menu contains all functions required for configuring the device.
Press the fifth softkey ("...continue") to branch to further configuration functions.
5.4.6.2 Analog output (function 70)
7O Analog output O
2
4 - 2O mA
output inverted
Suppress negative
measured values
Figure 5-47 Configuring the analog output
With this function, you can configure the analog output.
With softkey 1, define the start-of-scale value of the analog current range. The following
settings (see also table "Configurations of the analog output") are possible:
0 – 20 mA
2 – 20 mA
4 – 20 mA
NAMUR/4 – 20 mA (with limit at 3.8 mA).

Table of Contents

Other manuals for Siemens OXYMAT 64

Related product manuals