Siemens
RDF301, RDF301.50..., RDF600KN
Building Technologies
3.3.2
Room temperature setpoints can be
set during commissioning
adjusted during runtime
The source ca
the local HMI
a tool
a central control unit
The thermostat stores the setpoints
in EEPROM in the form of parameters
in the runtime memory
The table below shows the interrelations:
Setpoint setting
Commis
sioning
– HMI
– Tool download
Input
Comfort basic setpoint
Dead zone Comfort
1)
Setpoints Heating
Setpoints Cooling
Setpoint Economy Heating
Setpoint Economy Cooling
Setpoints Heating
Setpoints Cooling
Setpoint Protection Heating
Setpoint Protection Cooling
Current
runtime
setpoints in
thermostat
Input
Mode
Comfort setpoint
Setpoint shift H
Setpo
Economy Heating
Economy Cooling
Setpoint shift H
Setpo
Protection Heating
Protection Cooling
Effective room operating mode
1)
Only required for heating AND cooling applications
2)
LTE Mode
3) S-
Mode:
The
current
on the bus for
Comfort basic setpoint
Comfort setpoint
Economy heating
setpoint
Economy cooling
setpoint
Current setpoint
RDF301, RDF301.50..., RDF600KN
, RDF600KN/S Basic D
ocumentation
3.3.2
Setting and adjusting setpoints
Room temperature setpoints can be
set during commissioning
adjusted during runtime
The source ca
n be
the local HMI
a tool
a central control unit
The thermostat stores the setpoints
in EEPROM in the form of parameters
in the runtime memory
The table below shows the interrelations:
Setpoint setting
Stored in EEPROM
of thermostat
Input
LTE Mode
Input
S
-
Mode
Setpoints Heating
Setpoints Cooling
Comfort basic setpoint
P08 Comfort basic setpoint
P33 Dead zone Comfort
Setpoints Heating
Setpoints Cooling
P11
P12
P65 Protection Heating
P66 Protection Cooling
Setpoint
adjustment
Input
LTE
Mode
2)
Input
S
-
Mode
3)
Local ope
-
ration
Setpoint shift H
Setpo
int shift C
Comfort setpoint + / - buttons
Setpoint shift H
Setpo
int shift C
Current setpoint (used by the
thermostat for temperature control)
Only required for heating AND cooling applications
(see
LTE Mode
: the shift is added to the local shift.
Mode:
the last intervention wins, either S-
Mode input or local operation
current
setpoint
(used by the thermostat for temperature control
on the bus for
use in the central control unit.
27 / 94
ocumentation
CE1P3171en
2017-12-07
Stored in EEPROM
of thermostat
P08 Comfort basic setpoint
P33 Dead zone Comfort
1)
P11
Economy Heating
P12
Economy Cooling
P65 Protection Heating
P66 Protection Cooling
New
current
runtime setpoints
in thermostat
Comfort setpoint
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
thermostat for temperature control)
(see
section 3.6.8).
Mode input or local operation
.
(used by the thermostat for temperature control
) is available

Table of Contents

Other manuals for Siemens RDF301.50 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF301.50 Series and is the answer not in the manual?

Siemens RDF301.50 Series Specifications

General IconGeneral
BrandSiemens
ModelRDF301.50 Series
CategoryThermostat
LanguageEnglish

Related product manuals