70 / 94
Siemens RDF301, RDF301.50..., RDF600KN, RDF600KN/S Basic Documentation CE1P3171en
Building Technologies 2017-12-07
3.14.3 Parameters of the "Service level"
Parameter
Name Factory setting Range
RDF301..
RDF600KN…
Dependencies
P01 Control sequence
2-pipe:
1 = Cooling only
4-pipe:
4 = Heating and Cooling
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
P02
Operation via room op
selector
1 1 = Auto – Protection
2 = Auto - Comfort - Economy –
Protection
P01
P04 Unit 0
0 = °C
1 = °F
P05 Measured value correction 0 K – 3 ... 3 K
P06 Standard display 0
0 = Room temperature
1 = Setpoint
P07
Additional display
information
0
0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12h) (via bus)
4 = Time of day (24h) (via bus)
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Comfort setpoint minimum 5 °C 5 ... 40 °C
P10 Comfort setpoint maximum 35 °C 5 ... 40 °C
P11 Economy heating setpoint 15 °C
OFF, 5 ... WCoolEco;
WCoolEco = 40 °C max
P12 Economy cooling setpoint 30 °C
OFF, WHeatEco ... 40 °C;
WHeatEco = 5C min
P13
Electric heater when
cooling
ON
ON: Enabled
OFF: Disabled
Appl.
P14 Button lock 0
0 = Unlocked
1 = Auto lock
2 = Manual lock
P15
Fan stage in dead zone
(Comfort)
(RDF600KN)
4)
0 0 = Disabled
1 = Low speed (Heat and Cool)
2 = Low speed (Cooling only)
x
4)
Not available on RDF600KN SW < V1.8
Parameter display depends on selected application and function.
Note: