RDF301, RDF301.50..., RDF600KN
Building Technologies
3.9
The
) can be connected to the input terminals. The functionality of
be configured via parameters P38
The current temperature or
The parameters can be set to the following values:
Heating/
cooling
changeover
2
RDF301, RDF301.50..., RDF600KN
has 2 multifunctional inputs X1 and X2.
type sensor like the QAH11.1 (AI, analog input
) can be connected to the input terminals. The functionality of
be configured via parameters P38
The current temperature or
state of the inputs X1/X2 is
The parameters can be set to the following values:
Sensor input for external room temperature sensor or
return air temperature sensor to acquire the current
room temperature, or floor heating temperature
sensor to limit the heating output.
Note: The room temperatu
re is acquired by the built
sensor if the floor temperature limitation function is
enabled via parameter P51.
Sensor input for "Automatic heating /
changeover" function.
A switch can also be connected rather than a sensor
Important: Switch closed means always cooling, (this
cannot be changed), see section 3.5
Heating / cooling changeover is also possible via bus.
this case, the function must not be assigned to any
local input X1, X2. See also section
is displayed for closed contact /
100 for open contact, if a switch is connected.
to switch the operating mode to
Protection.
If the window contact is open
ineffective and "OFF" is displayed.
Window contact is also possible via bus. In this case,
the function must not be assigned to any local input
X1, X2. See also section 3.2.1.
Digital input to switch over the operating mode to
If the operating mode switchover contact is active,
user operations are ineffective and "
Operating mode switchover is also possible via bus.
In this case, the function must not be assigned to any
local input X1, X2. See also section
Digital input for a dew point sensor to detect
condensation. Cooling is stopped if
) can be connected to the input terminals. The functionality of
Sensor input for external room temperature sensor or
return air temperature sensor to acquire the current
room temperature, or floor heating temperature
re is acquired by the built
sensor if the floor temperature limitation function is
A switch can also be connected rather than a sensor
Important: Switch closed means always cooling, (this
Heating / cooling changeover is also possible via bus.
this case, the function must not be assigned to any
is displayed for closed contact /
100 for open contact, if a switch is connected.
to switch the operating mode to
Window contact is also possible via bus. In this case,
the function must not be assigned to any local input
Digital input to switch over the operating mode to
If the operating mode switchover contact is active,
Operating mode switchover is also possible via bus.
In this case, the function must not be assigned to any
Digital input for a dew point sensor to detect