Parameter
Name Factory setting Range
RDF301..
RDF600KN,
RDF600KN/VB
Dependencies
Expert level
P51
Flow temp limit floor
heating
OFF OFF, 10...50 °C
ü ü
P38, P40
P52 Fan control 1
0 = Disabled
1 = Enabled
2 = Heating only
3 = Cooling only
ü ü
P53 Fan speeds 3-speed
1 = 1-speed
2 = 3-speed
ü ü
P52
P54 Fan overrun time 60 sec 0...360 sec
ü ü
P52, Appl.
P55
Fan speed switching point
high
100% 80...100%
ü ü
P52, P53,
DIP
P56
Fan speed switching point
med
65% 30..75%
ü ü
P52, P53,
DIP
P57
Fan speed switching point
low
10% 1...15%
ü ü
P52, P53,
DIP
P58 Fan start kick ON
ON: Enabled
OFF: Disabled
ü ü
P52
P59 On time minimum fan 2 min 1...6 min
ü ü
P52
P60
6)
Periodic fan kick Comfort
RDF301...
RDF600KN,
RDF600KN/VB
0
OFF
0…89 min, OFF(90
*)
)
ü
x
x
ü
P52
P61 Periodic fan kick Eco OFF 0…359 min, OFF(360
*)
)
ü ü
P52
P62 Service filter OFF (0
*)
) OFF, 100…9900 h
ü ü
P52
P65
Protection heating
setpoint
8 °C
OFF, 5…WCoolProt;
WCoolProt = 40 °C max
ü ü
P66 Protection cooling setpoint OFF
OFF, WHeatProt… 40;
WHeatProt = 5°C min
ü ü
P67
Fan start delay
(RDF600KN,
RDF600KN/VB )
4)
0 s 0...360 s x
ü
P52, P46
P68 Temporary Comfort mode 0 (= OFF) 0...360 min
ü ü
P02
P69
Temporary Comfort
setpoint
OFF
OFF = Disabled
ON = Enabled
ü ü
P71 Restore factory setting OFF
OFF = Disabled
ON = Reload start
"8888" is displayed for 3s during
reload process
ü ü
P77 Presence detection
1 = Standard presence
mode
1 = Standard presence mode
2 = Hotel presence mode
x
ü
*)
The numbers are displayed in ACS tool
4)
Not available on RDF600KN, RDF600KN/VB SW < V1.8
5)
On RDF600KN, RDF600KN/VB SW < V1.8, setting range 0…8
6)
On RDF301 and RDF301.50, it is recommended that the fan is running in deadzone, i.e.
P60=0, or using a return air- or external temperature sensor.