Siemens RDF301, RDF301.50..., RDF600KN, RDF600KN/S Basic Documentation CE1P3171en
Building Technologies 2017-12-07
3.14 Control parameters
A number of control parameters can be readjusted to optimize control performance.
This can be done on the thermostat via HMI or via commissioning / operating tool.
These parameters can also be set during operation without opening the unit.
In the event of a power failure, all control parameter settings are retained, see page 53.
The control parameters are assigned to 2 levels:
"Service level", and
"Expert level" including communications, diagnostics and test.
The "Service level" contains a small set of parameters to set up the thermostat for
the HVAC system and to adjust the user interface. These parameters can be
adjusted any time.
Change parameters at the "Expert level" carefully, as they impact the thermostat’s
control performance and functionality.
3.14.1 Parameter setting via local HMI
1. Press buttons + and – simultaneously for 4 seconds.
Release and press button + again within 2 seconds until the display shows "P01".
Continue with step 2.
1. Press buttons + and – simultaneously for 4 seconds.
Release and press button – again within 2 seconds until the display shows "P01".
2. Repeatedly press the + or button to select the required parameter.
P01
P02 P08 P14
+- +
- -
+
3171z99
End
-
+
-
P13
+-
3. Press + and simultaneously. The current value of the selected parameter
begins to flash, allowing you to change the value by repeatedly pressing + or .
4. The next parameter is displayed when you press + and again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters.
6. Press + or – until "End" is displayed, and then press + and – simultaneously to
save the change and exit parameter entry mode.
The factory setting for the control parameters can be reloaded via parameter P71,
by changing the value to "ON", and confirming by pressing buttons + and
simultaneously. The display shows "8888" during reload.
Enter only "Service"
level
Enter "Service" and
"Expert" level.
Adjust parameters
Reset parameters

Table of Contents

Other manuals for Siemens RDF301.50 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF301.50 Series and is the answer not in the manual?

Siemens RDF301.50 Series Specifications

General IconGeneral
BrandSiemens
ModelRDF301.50 Series
CategoryThermostat
LanguageEnglish

Related product manuals