EasyManuals Logo

Siemens RDF301.50 Series Basic Documentation

Siemens RDF301.50 Series
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
76 / 94
Siemens
RDF301, RDF301.50..., RDF600KN
Building Technologies
The thermostat's control parameters can
the entire system
The parameters can be adjusted using
Local HMI
Synco ACS
– ETS
Commissioning
possible with ETS)
The control parameters of the thermostat can be set to ensure optimum
performance of the entire system (see
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting is as follows:
Application
2-
pipe and chilled /
4-
pipe, chilled ceiling and radiato
When the thermostat is used with a compressor, adjust the minimum output on
time (parameter P48) and
damaging the compressor or shortening its life due to frequent switching
Recalibrate the t
thermostat does not match the room temperature measured
of operation)
We recommend to review the setpoints and s
P08…P12) and change them as needed to achieve maximum comfort and save
energy
.
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press buttons
programming mode, which is indicated on the display with
Programming mode remains active until thermostat identification is complete.
Assign device address (P81) via HMI, ACS or ETS
With device address set to 255, the communication is deactivated (no exchange of
process data).
Use ETS
to assign the KNX group addresses of the
objects.
RDF301.50
which must be configured via ETS. The switching groups only work
Each device has a unique KNX serial number inside
sticker with the same KNX serial number is enclosed in the packaging box. This
sticker is intended for installers for documentation purposes.
Control parameters
Control sequence
Compressor-based
applications
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX device
address
Assign KNX group
addresses
Switching groups
RDF301.50...and
RDF600KN/S only
KNX serial number
RDF301, RDF301.50..., RDF600KN
, RDF600KN/S Basic D
ocumentation
The thermostat's control parameters can
be set to ensure optimum perfor
the entire system
.
The parameters can be adjusted using
Local HMI
Synco ACS
Commissioning
of switching groups for RDF301.50…and
RDF600KN/S
possible with ETS)
.
The control parameters of the thermostat can be set to ensure optimum
performance of the entire system (see
section 3.14).
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting is as follows:
Application
Factory setting P01
pipe and chilled /
heated ceiling 1 = c
ooling only
pipe, chilled ceiling and radiato
r 4 =
h
When the thermostat is used with a compressor, adjust the minimum output on
time (parameter P48) and
OFF-
time (parameter P49) for Y11/Y21 to avoid
damaging the compressor or shortening its life due to frequent switching
Recalibrate the t
emperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured
of operation)
. To do this, change parameter P05.
We recommend to review the setpoints and s
etpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
.
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press buttons
"operating mode" and "+"
simultaneously for 6 sec to activate
programming mode, which is indicated on the display with
"PrO
Programming mode remains active until thermostat identification is complete.
Assign device address (P81) via HMI, ACS or ETS
.
With device address set to 255, the communication is deactivated (no exchange of
process data).
to assign the KNX group addresses of the
thermostat's
RDF301.50
and RDF301.50H have
2 switching groups with a pair of buttons each,
which must be configured via ETS. The switching groups only work
Each device has a unique KNX serial number inside
the front panel. An additional
sticker with the same KNX serial number is enclosed in the packaging box. This
sticker is intended for installers for documentation purposes.
ocumentation
CE1P3171en
2017-12-07
be set to ensure optimum perfor
mance of
RDF600KN/S
is only
The control parameters of the thermostat can be set to ensure optimum
The control sequence may need to be set via parameter P01 depending on the
Factory setting P01
ooling only
h
eating and cooling
When the thermostat is used with a compressor, adjust the minimum output on
-
time (parameter P49) for Y11/Y21 to avoid
damaging the compressor or shortening its life due to frequent switching
.
emperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured
(after min. 1 hour
etpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
The programming mode helps identify the thermostat in the KNX network during
simultaneously for 6 sec to activate
"PrO
g
".
Programming mode remains active until thermostat identification is complete.
With device address set to 255, the communication is deactivated (no exchange of
thermostat's
communication
2 switching groups with a pair of buttons each,
which must be configured via ETS. The switching groups only work
in S-Mode.
the front panel. An additional
sticker with the same KNX serial number is enclosed in the packaging box. This
sticker is intended for installers for documentation purposes.

Table of Contents

Other manuals for Siemens RDF301.50 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF301.50 Series and is the answer not in the manual?

Siemens RDF301.50 Series Specifications

General IconGeneral
BrandSiemens
ModelRDF301.50 Series
CategoryThermostat
LanguageEnglish

Related product manuals