Appendix
A.3 Electrical tests (EEC devices)
SCALANCE X-300
278 Operating Instructions, 10/2010, A5E01113043-10
Figure A-4 Releasing the RJ-45 plug with a screwdriver (based on the example of the IE FC RJ-45
Plug 180)
A.3 Electrical tests (EEC devices)
Regulations / standards
IEC 60255 (product standards)
IEEE C37.90.0/.1/.2
UL 508
Further standards: See individual tests.
Insulation test
Relevant standards: IEC 60255-5 and IEC 60870-2-1
Voltage test (routine test) for all circuits except communications and time synchronization
interfaces 2.5 kV (eff) 50 Hz / 3.5 kV DC
Voltage test (routine test) only for protected communications interfaces 500 V (eff) 50 Hz /
707 V DC
Voltage test (routine test) for all circuits except communications interfaces, class III 5 kV
(peak); 1.2/50 μs; 0.5 J
EMC tests of immunity (type tests)
Relevant standards: IEC 60255-6 and -22 (product standards), EN 61000-6-2 (generic
standard)
High frequency test IEC 60255-22-1, class III / IEEE C37.90.1, 2.5 kV (peak); 1 MHz
Discharge of static electricity IEC 60255-22-2, class IV and IEC 61000-4-2, class IV 8 kV
contact discharge; 15 kV air discharge
Radiated electromagnetic field disturbance, frequency sweep IEC 60255-22-3, class III
IEC 61000-4-3, class III 10 V/m; 80 MHz to 1000 MHz; 80 % AM; 1 kHz 10 V/m; 800 MHz to
960 MHz; 80 % AM; 1 kHz 20 V/m; 1.4 GHz to 2.0 GHz; 80 % AM; 1 kHz
Irradiation with RF field, single frequencies IEC 60255-22-3, IEC 61000-4-3, class III –
amplitude modulated – pulse modulated 10 V/m 80/160/450/900 MHz; 80 % AM; 1 kHz
Fast transients / burst IEC 60255-22-4 and IEC 61000-4-4 and IEEE C37.90.1 class IV 4 kV