Commissioning
6.3 Parameterizing the device
PAC2200
64 Manual, 05/2018, L1V30415167B-02
"Write protection" parameter
The "Write protection" parameter is described later in this chapter.
"Date/Time" parameter
The date and time can be set by using the "Date/time" option in the "Settings" menu.
Date:
Displayed in accordance with the format
Format:
DD.MM.YYYY (default setting)
MM/DD/YY
YYYY-MM-DD
Time:
HH:MM:SS
Time zone:
00:00 range:
-12:00 ... +14:00,
settable in 30 minute steps.
Daylight saving:
Automatic change of time from standard time to daylight
saving time and from daylight saving time to standard time.
OFF:
Time change is switched off (default setting)
Auto EU:
Time change within the European Union, changeover to
daylight saving time: The internal clock is put forward from 1
a.m. UTC to 2 a.m. UTC on the last Sunday in March.
Changeover to winter time: The internal clock is put back
from 2 a.m. UTC to 1 a.m. UTC on the last Sunday in Oct
o-
ber.
Auto US:
Time change within the USA, changeover to daylight saving
time: The internal clock is put forward from 2 a.m. local time
to 3 a.m. on the second Sunday in March. Changeover to
winter time: The internal clock is put back from 2 a.m. local
time to 1 a.m. on the first Sunday in November.
Table:
Time change can be individually parameterized. The p
a-
rameters can be set in the software.
SNTP (with Ethernet interface
only):
Protocol is used for transmitting the time and for synchron
i-
zation.
OFF: SNTP function deactivated (default setting)
ACTIVE: Date/time synchronization via NTP server
IP (only when SNTP is
activated):
0.0.0.0 (default setting)
If an SNTP IP address is configured, only data from this IP
address is accepted.