Commissioning
6.3 Parameterizing the device
PAC2200
Manual, 05/2018, L1V30415167B-02
65
"Integrated I/O" parameter
"Digital input" parameter
The following functions can be assigned to the "Digital input" parameter:
● Tariff switching for two-tariff, active energy, and reactive energy counters.
● Synchronization of the measuring period by means of the synchronization pulse of a
system control center or other device.
Not used: Digital input is deactivated.
: Counting of input pulses
High tariff / low tariff switching
: Switching between tariffs.
Low tariff if input active.
: Synchronization of power de-
Default setting: Not used.
The "UNIT" property is only visible if "Count input pulses"
is set for the "USAGE TYPE".
Countable unit with pulse counting:
Active Energy (kWh)
Reactive Energy (kvarh)
UNIT
The "PULSES PER UNIT" property is only visible if "Count
input pulses" is set for the "USAGE TYPE".
PRO (input pulse divider)
The "Input pulse divider" property is only visible if "Count
input pulses" is set for the "USAGE TYPE".
:
se divider: 100