Commissioning
6.3 Parameterizing the device
PAC2200
66 Manual, 05/2018, L1V30415167B-02
"Digital output" parameter
The following functions can be assigned to the "Digital output" parameter:
● Energy pulse output; can be programmed for active or reactive energy pulses
● Indication of the direction of rotation
● Operating state display of the device
● Switching output for remote control via the interface
Not used: Digital output is deactivated.
: Digital output is activated.
: The digital output is controlled by remote
: Digital output is switched on by an
-clockwise rotating field and remains active
for as long as the field is rotating in this direction.
: Digital output signals the number of pulses
set for each energy unit (e.g. kWh). The energy counter
specified in the "COUNTER SOURCE" field is eva
luated
Default setting: Not used
The "PULSES PER UNIT" property is only visible if "Energy
pulse" is set for the "USAGE TYPE".
PRO (output pulse divider)
The "Output pulse divider" property
is only visible if "Energy
pulse" is set for the "USAGE TYPE".
Selects the type of cumulative power and the import value
that triggers the pulse when that value is reached.
Range: Counter import active energy (kWh), counte
r export
active energy (kWh), counter import reactive energy (kvarh),
counter export reactive energy (kvarh)
Default setting: Counter Import Active Energy (kWh)
The "COUNTER SOURCE" property is only visible if "Ene
r-
gy pulse" is set for the "USAGE TYPE".
Duration of the energy pulses.
The "PULSE DURATION" property is only visible if "Energy
pulse" is set for the "USAGE TYPE".