Technical data
8.1 Technical data
PAC2200
76 Manual, 05/2018, L1V30415167B-02
Measuring inputs for voltage (5 A device)
Measuring inputs
Voltage U
n
220/230 VAC 50 / 60 Hz (MID devices only 50 Hz)
Max. measurable voltage
Voltage L-N
AC 3~ 230 V (+20%)
Voltage L-L
AC 3~ 400 V (+20 %)
Min. measurable voltage
Voltage L-N
AC 3~ 230 V (-80%)
Voltage L-L
AC 3~ 400 V (-80%)
Zero point suppression level
Voltage L-N
7 V
Voltage L-L
10 V
Impulse withstand voltage
6.5 kV (1.2/50 μs)
Measuring category
CAT III (acc. to IEC 61010-2-030)
Input resistance (L-N)
1
Max. power consumption per phase
80 mW
Measuring inputs for current (5 A device)
Only for connection to AC power systems via external current transformers (5 A device)
Measuring inputs
Rated current In I
e
1 A / 5 A
Max. permissible continuous current
10 A
Current impulse overload capability
100 A for 1 s
Zero point suppression level
1 mA / 5 mA
Max. power consumption per phase
500 mVA at 6 A
Measuring range
1 ... 120%
Measuring inputs (65 A device)
For direct connection to the AC system.
Measuring inputs
Reference current Iref
10 A
Max. input current Imax
65 A
Maximum power consumption 0.4 VA / phase
Measuring range 0.5 ... 65 A