Technical data
8.1 Technical data
PAC2200
Manual, 05/2018, L1V30415167B-02
77
Measuring accuracy
Standards applied
IEC 61557-12
IEC 62053-21
IEC 62053-22
IEC 62053-23
EN 50470-3:
Measured variable
Accuracy class acc. to IEC 61557-12 (K55)
Voltage
Class 0.5
Current
Class 0.5
Apparent power
Class 1
Active power
Class 1
Reactive power
Class 1
Total apparent power over all phases
Class 1
Total active power over all phases
Class 1
Total reactive power VAR1 over all phases
Class 2
Cumulated active power
Class 1
Cumulated reactive power
Class 2
Total power factor
Class 0.5
Line frequency
Class 0.05
Active energy
Class 1
Reactive energy
Class 2
Active energy according to IEC62053-21
Class 1
Reactive energy according to IEC62053-23
Class 2
Measurement accuracy according to EN50470-3
Class B
Note:
For the PAC2200 (5A) device, the accuracy of the measurement depends on the quality of
the current transformers used.
Digital input
Digital input
Number
1
Type
Passive
Maximum switching voltage
30 V
Input current
"1" signal detection 2.510 mA
"0" signal detection ≤0.5 mA