EasyManua.ls Logo

Siemens SENTRON PAC2200 - Page 81

Siemens SENTRON PAC2200
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
8.1 Technical data
PAC2200
Manual, 05/2018, L1V30415167B-02
79
Connection elements
The specified conductor cross sections describe the capacity of the connection terminals.
When selecting the conduction cross sections, always pay attention to the possible current
load and ensure adequate cable protection.
Current, power supply
5 A device
65 A device
Conductor cross section
Rigid
0.2 ... 6 mm
2
0.75 ... 35 mm
2
Flexible
0.2 ... 4 mm
2
1 ... 35 mm
2
Flexible with end sleeve, without plastic
sleeve
0.2 ... 4 mm
2
0.75 ... 25 mm
2
Flexible with end sleeve and plastic
sleeve
0.25 ... 4 mm
2
0.75 ... 25 mm
2
AWG
24 ... 10
19 ... 2
2-wire, same cross-section
Rigid
0.2 ... 1.5 mm
2
0.75 ... 10 mm
2
Flexible
0.2 ... 1.5 mm
2
1 ... 4 mm
2
Flexible with end sleeve, without plastic
sleeve
0.25 ... 0.75 mm
2
0.75 ... 4 mm2
Flexible with TWIN end sleeve and plastic
sleeve
0.5 ... 2.5 mm
2
0.75 ... 4 mm
2
AWG
24 ... 14
19 ... 8
Tightening torque 0.5 ... 0.6 Nm [4.4
...5.3 lb-in]
3 Nm [26.6 lb-in]
Communication ports
Conductor cross section
Rigid
0.14 ... 1.5 mm
2
Flexible
0.14 ... 1.5 mm
2
Flexible with end sleeve, without plastic
sleeve
0.25 ... 1 mm
2
Flexible with end sleeve and plastic
sleeve
0.25 ... 1.5 mm
2
AWG
26 ... 16
2-wire, same cross-section
Rigid
0.14 ... 0.75 mm
2
Flexible
0.14 ... 0.75 mm
2
Flexible with end sleeve, without plastic
sleeve
0.25 ... 0.5 mm
2
Flexible with TWIN end sleeve and plas-
tic sleeve
0.5 ... 1 mm
2
AWG
26 ... 18
Tightening torque
0.5 ... 0.6 Nm [4.4 ...5.3 lb-in]

Table of Contents