EasyManua.ls Logo

Siemens SICLOCK TC 400

Siemens SICLOCK TC 400
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterization
9-84
© Siemens AG 2007 All Rights Reserved
SICLOCK
®
TC 400
Daylight saving time
The daylight saving time changeover is automatically performed by the device at
the parameterized times.
/Time/Advanced/Daylight Saving Time (0.09.07)
parameter
With the setting "enable = no", the time changeover is suppressed and the plant
is operated with standard time.
The calendrical regulation for the daylight saving time changeover can be speci-
fied worldwide via a parameter.
Leap seconds
Use the /Time/Advanced/Leap Seconds[20] (0.09.05) parameter to specify the
calendar of leap seconds.
9.3.2 Synchronization
Synchronization status
You can read out different information about the current synchronization status
via the /Synchronization/Status of Synchronization (0.09.09)
parameter.
Protected synchronization
If a discontinuity of more than 5 s occurs in the external synchronization, the pro-
tected synchronization is activated. The synchronization is suppressed and an
alarm issued which is present as long as there is a discontinuity in the external
synchronization.
The pending synchronization suppression can be ignored once and the "Pro-
tected synchronization" alarm cleared with the parameter entry /Synchroniza-
tion/Advanced/Protected Synchronization/ignore /clear alarm (0.09.12) = "yes".
Note
The preset changeover times correspond to the present valid regulations of the
European Community.
Notice
This initiates an unconditional synchronization to the external time and an incon-
sistency in the time distribution to the plant can result.
If required, disconnect the active external synchronization first or delete the server
address for the NTP client operation from the /NTP Client/NTP Server List[4]
(0.18.02) parameter.

Table of Contents