Technical specifications
12.1 Standards and approvals
CPU 1515SP PC2 (F/T/TF)
68 Operating Instructions, 09/2018, A5E42603425-AA
cULus HAZ. LOC. approval
Underwriters Laboratories Inc., complying with
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 142 (Process Control Equipment)
ANSI/ISA 12.12.01
CSA C22.2 No. 213 (Hazardous Location)
APPROVED for use in
Class I, Division 2, Group A, B, C, D Tx;
Class I, Zone 2, Group IIC Tx
Installation Instructions for cULus haz.loc.
WARNING - Explosion Hazard - Do not disconnect while circuit is live unless area is
known to be non-hazardous.
WARNING - Explosion Hazard - Substitution of components may impair suitability for
Class I, Division 2 or Zone 2.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class I,
Zone 2, Group IIC; or non-hazardous locations.
WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING
PROPERTIES OF MATERIALS USED IN THE RELAY.
FM approval
Factory Mutual Research (FM) according to
Approval Standard Class Number 3611, 3600, 3810
(ANSI/ISA 82.02.01)
CSA C22.2 No. 213
CSA C22.2 No. 61010-1
APPROVED for use in Class I, Division 2, Group A, B, C, D Tx;
Class I, Zone 2, Group IIC Tx
Installation Instructions for FM
WARNING - Explosion Hazard - Do not disconnect while circuit is live unless area is
known to be non-hazardous.
WARNING - Explosion Hazard - Substitution of components may impair suitability for
Class I, Division 2 or Zone 2.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class I,
Zone 2, Group IIC; or non-hazardous locations.
WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING
PROPERTIES OF MATERIALS USED IN THE RELAYS.
OR