Installing and connecting the device
3.3 Connecting the device
SIMATIC IPC377G
Operating Instructions, 07/2022, A5E51366314-AB
33
Procedure
Clamp the cable lug on the function earth.
Firmly attach the cable lug to the function earth connection
on the device using the M4 thread (see part labeled).
Connect the function earth to the function earth connection
of the cabinet or the plant in which the device is installed.
3.3.3 Connecting the power supply
Note
The equipment is designed for operation with Safety Extra
-Low Voltage (SELV) or Protective
Extra-Low Voltage (PELV).
Note
The 24 V DC power supply must be adapted to the input data of the device (see
Technical
specifications
(Page 61)).
Requirements
The function earth is connected.
You are using the supplied terminal.
A two-core cable meets the following requirements:
a copper (Cu) cable cross-section of 0.75 mm
2
to 2.5 mm
2
rated temperature 75 °C
Tightening torque: 0.56 Nm
A slotted screwdriver with approximate 3 mm blade.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC IPC377G and is the answer not in the manual?

Siemens SIMATIC IPC377G Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC IPC377G
CategoryIndustrial PC
LanguageEnglish

Related product manuals