Maintaining and repairing the device
7.3 Cleaning the Device Front
SIMATIC IPC377G
Operating Instructions, 07/2022, A5E51366314-AB
51
Cleaning Agents
NOTICE
Damage to the front panel caused by impermissible cleaning agents
Impermissible and unsuitable cleaning agents may cause damage to the front panel.
Only use a damp cloth for cleaning. Do not use the following cleaning agents:
Aggressive solvents or scouring powder
Steam jets
Compressed air
Procedure
1. Switch off the device. This will not inadvertently trigger functions when touching the screen
and/or the membrane keypad.
2. Moisten only the cleaning cloth, do not spray liquids directly onto the device.
3. Clean the enclosure surface with a damp cloth and make sure that no water enters the
device.