Performance data   
2.4 Characteristics of open TCP/IP communication 
  CP 443-1 Advanced (GX30) 
28  Manual, 03/2019, C79000-G8976-C256-05 
Table 2- 2  Dependency of the maximum number of RECEIVE calls long (AG_LRECV FC60) used at the same time on 
the number of SEND calls (CPU 416/417) 
Number of simultaneous 
SEND calls 
Max. number of simulta-
neous FC60s per 
51  50  49  48  47  46  45  44  43  42  41  40  39  38 
Number of simultaneous 
SEND calls 
 
 
 
 
 
 
 
 
 
   
Max. number of simulta-
neous FC60s per 
37  36  35  34  33  32  31  30  29  28  27  26  25   
The maximum number of SPEED SEND/RECEIVE calls that can be used simultaneously 
(FC53, FC63) depends only on the CPU (see above). 
 
Characteristics of open TCP/IP communication 
Open TCP/IP communication provides a program interface for the transfer of connection-
oriented and connectionless services. The establishment and termination of connections is 
initiated here only via the "dynamic" program interface. 
The CP supports communication via ISO-on-TCP connections for this interface. 
Table 2- 3  Open TCP/IP communication 
Number of dynamically generated connections over Indus-
•  ISO-on-TCP connections: 1...64 
 
Characteristic data for PROFINET IO 
PROFINET IO communication of the CP is IRTcompliant. The CP supports the following 
maximum configuration as a PROFINET IO controller: 
 
Number of CPs that can be operated as PROFINET IO 
controllers within an S7400 station 
4 
Number of possible PROFINET IO devices 
*)
  128 
*)
, of which 
•  up to 64 in IRT mode 
•  up to 32 in "prioritized startup" mode 
Size the input area over all PROFINET IO devices 
Size of the output area over all PROFINET IO devices