Configuration and operation   
6.7 PROFINET IO mode 
  CP 443-1 Advanced (GX30) 
76  Manual, 03/2019, C79000-G8976-C256-05 
You specify the required synchronization parameters in the "Synchronization" parameter 
group of the PROFINET interface. 
 
Note 
Requirements for configuration 
Configuration for IRT communication
 is only possible with STEP 7 V5.5.x. 
 
Operating PROFINET IO devices with a current firmware version 
Using current firmware versions 
For the PROFINET IO devices listed below, you should use the current firmware versions to 
operate the CP. 
●  IM151-3PN with article number 6ES7151-3AA20-0AB0 
●  IM151-3PN with article number 6ES7151-3BA20-0AB0 
You will find the current firmware versions on the Internet at the following address: 
Link: (https://support.industry.siemens.com/cs/ww/en/view/22810435)  
 
Shared device - using the router address 
Shared devices allow more than one PROFINET IO controller to access different 
submodules of the same PROFINET IO device. 
CP as PROFINET IO controller with shared device 
The information below applies if all the following requirements are met: 
●  The CP is used as a PROFINET IO controller with an assigned shared device. 
●  No router is configured on the PROFINET interface. 
●  The gigabit interface of the CP is networked. 
 
In this case, the shared device is automatically assigned the IP address of the PROFINET 
interface of the CP as the router address. 
This assignment leads to a conflict when other IO controllers assigned to the shared device 
use other router addresses or no router address.