41 
 
When using the CP type described here, the following limits apply: 
●  Number of operable CPs within a rack: 14 
●  Number of CPs operating as PROFINET IO controllers within an S7 station: 4 
●  Number of CPs that can be configured for PROFINET CBA communication within an S7 
station: 1 
 
Note 
Number of CPs operating as PROFINET IO controllers 
The number of CPs operating as PROFINET IO controllers depends on the number of CP 
443
5 Extended modules operating as DP masters in the S7400 station. A total of 10 CPs 
can be operated as controllers for the distributed I/O (PROFINET IO controllers or DP 
masters); of those, however, only up to 4 a
s PROFINET IO controllers. 
Note the following regarding multiprocessor mode: When operating the CP as a 
PROFINET IO controller, only the process image of the assigned CPU can be distributed 
via the CP.
 
 
System environment 
General requirements 
●  The CP is released with CPUs as of firmware version V4.1. 
–  CPUs with firmware version 4.0 must be upgraded to V4.1. 
–  CPUs with firmware version 5.0 must be upgraded to V5.1. 
●  Open TCP/IP communication is supported by all CPUs as of firmware version V4.1. 
●  The program block PN_InOut_Fast (FB90) for PROFINET CBA is supported by all CPUs 
as of firmware version V4.1.