The configuration in the SIMATIC Manager appears as follows:
Configuring the AS in HW Config
1. Double-click the Hardware object in the detail view.
The HW Config dialog box opens.
2. Open the catalog and select the profile of the current PCS 7 version.
3. Insert the following objects of the SIMATIC 400 (Insert > Object menu command):
You can find information about the objects in the information section of the catalog.
Rack 400
PS 400
CPU 400 > CPU 400 H
Communication connections can be configured later. You can find information about
this in the following sections:
- Section "How to configure redundant PROFIBUS DP (Page 119)"
- Section "How to configure a high availability fieldbus on the basis of PROFINET
(Page 122)"
- Section "How to configure a media-redundant fieldbus on the basis of PROFINET
(Page 125)"
CP-400 (optional)
Communication connections can be configured later. You can find information on this
in the section "How to configure redundant communication processors (Page 111)".
Additional information
Manual
Automation System S7-400H; High Availability Systems
Advantages of high availability components
5.2 SIMATIC H station
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA 109