5.3.6 How to configure a media-redundant fieldbus on the basis of PROFINET
Introduction
The following section describes how to create and connect a media-redundant ring on the
basis of PROFINET.
Configure the components in HW Config.
In the Topology Editor, configure the connections between the components in accordance
with the cable sequence in the system.
Configure the media redundancy for the following modules:
CPU
IM
Requirements
The PCS 7 project with a SIMATIC station is open in SIMATIC Manager.
HW Config is open.
A rack with a PROFINET-capable module (CPU or CP) has been inserted in HW Config.
The PROFINET IO systems have been inserted at the PROFINET-capable modules (CPU
or CP). This can be done by inserting the PROFINET-capable module.
Configuring in HW Config
1.
2. In the hardware catalog, open the PROFINET IO > I/O > folder of the IO device type:
ET 200M
ET 200SP
ET 200SP HA
3. Select the version of the interface module (ET 200M: IM 153-4 ...; ET 200SP HA: IM 155-6-
PN/HA) you are using and move it onto the PROFINET IO system using drag-and-drop.
Advantages of high availability components
5.3 Communications connections
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA 125

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals