EasyManua.ls Logo

Siemens SIMATIC PCS 7 - Creating Custom Device Libraries

Siemens SIMATIC PCS 7
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation rules
The configuration always has to be symmetrical when using redundant I/O. Follow these
installation rules:
The first module in Redundant I/O must be placed at an odd-numbered slot on a terminal
block (TB45...).
Redundant modules are always identical (article number, firmware version, release)
,2
UHG
,2
UHG
,2
UHG
,2
UHG
,2
UHG
,2
UHG
Figure 4-1 Slot configuration by Redundant I/O
Configuration rules
Note
This type of redundant operation is possible only with certain I/O modules of the ET 200SP
HA. For additional information, please refer to the following documents:
Documentation
PCS 7 - Released Modules
Manual
Automation System S7-400H; High Availability Systems
Additional information
Section "Redundant interface modules in distributed I/O (Page 45)"
Section "Redundant I/O modules (Page 46)"
System manual
Distributed I/O System; ET 200SP HA
Manual
Automation System S7-400H; High Availability Systems
4.1.2 Switched I/O
Switched I/O
Switched I/O describes the situation when there is only one I/O module (SM) for processing a
process signal. The communication path to the I/O (station) is redundant. In the event that a
communication path fails, the distributed I/O (station) switches to the functioning
communication path. The non-redundant I/O modules of the distributed I/O can be addressed
via the redundant interface module (DP slave) of both central modules (CPU) of a high
availability system.
High availability solutions in PCS 7
4.1 Solutions for the I/O
High Availability Process Control Systems (V9.0)
42 Function Manual, 05/2017, A5E39221836-AA

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Related product manuals