7.7 OS clients
7.7.1 Switchover characteristics OS clients with permanent operability
Functionality
If the connection to the configured OS server is interrupted, the process values on the OS
clients are no longer updated. After successful switchover to the partner server, the process
can be operated again on all OS clients. Other OS clients interconnected with the redundant
OS partner server are not affected by this.
Example configuration
5HGXQGDQW26
VHUYHU
5HGXQGDQW26VHUYHU
SDLU
3HUPDQHQWRSHUDELOLW\
$XWRPDWLRQV\VWHPV
3ODQWEXV
26FOLHQW26FOLHQW
7HUPLQDOEXV
26VHUYHU
Permanent operability
If OS Server 1 fails, OS Client 1 is connected to redundant OS Server 2. The identity of the
redundant partner server of OS Server 1 comes from the downloaded server data on the OS
client. OS Client 1 is not available during the switchover to redundant OS Server 2 for a short
time. However, if redundant OS Server 2 is specified as the preferred server for OS Client 2,
you can operate the plant during the switchover from the failed OS Server 1 to redundant OS
Server 2.
Failure, switchover and reintegration of high availability components
7.7 OS clients
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA 213

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals