5.3.5 How to configure a high availability fieldbus on the basis of PROFINET
Introduction
The following section describes how to create and connect a high availability fieldbus on the
basis of PROFINET.
Configure the components in HW Config.
In the Topology Editor, configure the connections between the components in accordance
with the cable sequence in the system.
Requirements
The PCS 7 project with a SIMATIC H station is open in SIMATIC Manager.
HW Config is open.
The redundant backplane is inserted in HW Config.
In HW Config, each rack has been fitted with an 4xx-xH PN/DP H CPU and the required
synchronization modules.
The PROFINET IO systems are added to the H-CPU. This can be done using Insert on the
H‑CPU.
Configuring in HW Config
1. In the hardware catalog, open the PROFINET IO > I/O > folder of the IO device type:
ET 200M
ET 200SP
ET 200SP HA
2. Select the version of the interface module (ET 200M: IM 153-4 ...; ET 200SP HA: IM 155-6-
PN/HA) you are using and move it onto the PROFINET IO system using drag-and-drop.
Advantages of high availability components
5.3 Communications connections
High Availability Process Control Systems (V9.0)
122 Function Manual, 05/2017, A5E39221836-AA

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals