5.4.3 How to configure redundant input/output modules (PROFIBUS DP)
Introduction                         
You configure the redundant I/O modules using HW Config.
Note
Redundant operation is possible only with certain S7-300 I/O modules of the ET 200M. For 
additional information, please refer to the following documents:
● Documentation 
PCS 7 - Released Modules
● Manual 
Automation System S7-400H; High Availability Systems
Note
Only input/output modules with the same article number and the same product version in 
analog or digital version can be used. 
Assigning redundant modules
Redundant modules can be assigned to each other for the ET 200M as follows:
● The modules are located in two different ET 200M stations on the same redundant 
PROFIBUS DP (see sample configuration).
● The modules are located in two different ET 200M stations on different redundant 
PROFIBUS DPs.
● The modules are located in the same ET 200M station.
Advantages of high availability components
5.4 Distributed I/O
High Availability Process Control Systems (V9.0)
136 Function Manual, 05/2017, A5E39221836-AA