6. Optional steps for a redundant FOUNDATION Fieldbus:
These steps depend on the bus link that is used for the interconnection to the PROFIBUS DP:
1.
Select the following modules depending on the bus link used:
● for FF Link: "IM 153-2 FF" 
● for Compact FF Link: "IM 655-5 FF"
2. In the table, double click the slot of the first coupler depending on the bus link used.
● for FF Link: "FDC 157"
● for Compact FF Link: "Field Device Coupler"
The "Properties - Coupler" dialog box opens.
3. Select the "Parameters" tab.
4. Select the redundancy mode in the "Value" column:
● No redundant configuration (default)
● Coupler redundancy
● Ring redundancy
7. Click "OK".
The bus link is created with a FF subsystem.
Result
The following figure shows the resulting configuration in HW Config:
Additional information
● Operating Instructions 
SIMATIC; Bus Link; FF Link
● Operating Instructions 
SIMATIC; Bus Link; Compact FF Link