Redundancy connection
You need the following components to make the redundancy connection, depending on the
distance to be bridged:
Maximum distance Required components Connection
10 m Null modem cable Serial connection
100 m
● Crossover network cable
● Per server: A free network connection (see
section "Network components (Page 56)")
Ethernet connection
1000 m Fiber-optic cable
Per server:
● A free network connection
(see section "Network components
(Page 56)")
● 1 Ethernet cable
● 1 media converter
(e.g., SCALANCE X101-1)
Ethernet connection
Availability
The availability of the complete system is ensured even if one of the two OS servers fails
because the two OS servers form an independent redundancy node.
26VHUYHU
26VHUYHU
%XV%XV
Note
The buses marked with * (terminal bus and plant bus) can be configured redundantly with
optical or electronic switch modules.
Additional information
● Section "Network components (Page 56)"
● Section "How to configure an OS server and its redundant OS partner server (Page 152)"
● Online help for
WinCC
;
WinCC Redundancy
● Documentation on the Process Historian
High availability solutions in PCS 7
4.5 Solutions for OS servers
High Availability Process Control Systems (V9.0)
96 Function Manual, 05/2017, A5E39221836-AA