5.4.5 IE/PB LINK HA
The IE/PB LINK HA provides a connection of the redundant S7-1500 R/H system to PROFIBUS
DP.
The table below gives an overview of the main properties and functions.
Short designation
IE/PB LINK HA
Article number
6GK1411-5BB00 (as of FW version V4.1)
Equipment Manual
Bus system
PROFINET IO/PROFIBUS DP
Interface
PROFINET IO: RJ45
PROFIBUS DP: D-sub
PROFINET IO proxy (system redundancy as S2 device)
X (only with C-PLUG)
Time synchronization via SIMATIC/NTP mode
X
Data record routing
X
S7 routing
X
Data query using SNMPv1
X
LLDP
X
Media redundancy (MRP)
X
DP master class 2
X
Supported devices
1)
S7
DP V0
DP V1
Maximum number of DP Devices per IE/PB Link HA
S7-1500R: 63 (as S2 device)
S7-1500H: 64 (as S2 device)
Maximum number of DP inputs/DP outputs
2048 bytes (as S2 device)
Firmware update of the IE/PB LINK HA and the lower-level DP
devices using STEP 7
X
Maximum number of IE/PB links in the PROFINET network of
S7-1500R/H
S7-1500R: 15
S7-1500H: 63
Supported topologies of the IE/PB Link HA for S7-1500R/H
PROFINET network with S2 devices
in the PROFINET ring
in the line topology
via switches at ring or line topology
PROFINET network with R1 devices
via a Y-switch on the PROFINET rings
via a Y-switch on the line topologies
via switches at ring or line topology
1)
Fail-safe DP devices are not supported.