Application planning
6.2 Restrictions compared to the S7-1500 automation system
S7-1500R/H redundant system
132 System Manual, 01/2024, A5E41814787-AF
Requirement
Required STEP 7 version
S7-1500H(F):
Support of system redundancy R1
H-CPUs do not have to be part of a PROFINET ring or MRP do-
main.
This allows additional topology variants, such as line topology
or setup without additional devices.
SIMATIC STEP 7 Professional V18
or higher
R-CPUs: CP 1543-1 in the central configuration with a U-
connector
H-CPUs: CP 1543-1 in the central configuration with active
backplane bus
IE/PB Link HA
System power supply (PS)
SIMATIC STEP 7 Professional V19
or higher
6.2 Restrictions compared to the S7-1500 automation system
Introduction
Please note the following restrictions with the S7-1500R/H redundant system compared to
the S7-1500 automation system.
Hardware restrictions
Table 6- 3 Hardware restrictions
Property
Restriction
Fail-safe modules
No support for fail-safe modules on the 1513R-1 PN, 1515R-2 PN,
and 1517H-3 PN CPUs because no fail-safe variants of the CPUs are
available.
Fail-safe modules are only supported by the HF-CPUs.
Series machine projects, configu-
ration control (option handling)
Not supported
Central modules
The redundant S7-1500R/H system supports only the following
central modules:
Communications processor CP 1543-1
PS 25W 24V DC
PS 60W 24/48/60V DC
PS 60 W 120/230V AC/DC
Cycle and response times
Longer cycle and response times: You can find more information
in the Cycle and response times
(https://support.industry.siemens.com/cs/ww/en/view/59193558)
Function Manual.