Wiring
8.9 Connecting interfaces for communication with S7-1500H
S7-1500R/H redundant system
276 System Manual, 01/2024, A5E41814787-AF
Please see the following tables for the other specifications applicable to your specific
application.
Table 8- 4 Specifications for fiber-optic cables used indoors
Cabling
Necessary components
Specifications
Complete cabling routed
within a building.
No cable junction
between indoors and
outdoors.
Easy complete installa-
tion with pre-
assembled cables.
Patch cable for indoors
2 x duplex cables for the redundant system (connector type
LC/PC or LC/UPC, cores crossed):
Connector type in line with the other components.
Installation cable for indoor
use
4-core multicore cable for the redundant system (connector
type LC/PC or LC/UPC, cores crossed):
1 cable with 4 cores for the redundant system:
Both interfaces in one cable
1 or 2 cables with multiple shared cores for the redundant sys-
tem:
Interfaces laid separately to increase availability (reduction
of common cause factor)
Connector type in line with the other components
Table 8- 5 Specifications for fiber-optic cables used outdoors
Cabling
Necessary components
Specifications
A cable junction is re-
quired between the indoor
and outdoor area.
Installation through distri-
bution boxes (patch field).
Additional information can
be found in the section
below.
Installation cable for
outdoor applications (and
indoor applications)
Installation cable for outdoor use:
1 cable with 4 cores per S7-1500H system
Both interfaces in one cable
1 or 2 cables with multiple shared cores
Interfaces laid separately to increase availability (reduction
of common cause factor)
Connector type in line with the other components
Patch cable for indoors
Connector type in line with the other components.
Note
LC/APC connector type
The LC/APC connector type is not suitable for the fiber-optic cables.