EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 300

Siemens Simatic S7-1500
523 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
9.4 Configuring H-CPUs with PROFINET rings and R1 devices
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
299
3. Assigning IO devices to the redundant system
To assign R1 devices to the redundant S7-1500H system, connect each interface module of
the R1 device to each H-CPU.
The left interface module of each R1 device must be connected to the left H-CPU in the
network view. The right interface module of each R1 device must be connected to the right
H-CPU in the network view.
To do so, proceed as follows:
1. Switch to the network view.
2. Drag-and-drop a line between the PROFINET interface of the left interface module of the
ET200SP-R1_1 station and the PROFINET interface X1 of the left H-CPU.
3. Drag-and-drop a line between the PROFINET interface of the right interface module of the
ET200SP-R1_1 station and the PROFINET interface X1 of the right H-CPU.
4. Switch to the device view of the ET200SP-R1_1 station and set the watchdog timer for both
interface modules. To do this, navigate in the Inspector window to "Properties > PROFINET
interface [X1] > Advanced options > Real-time settings > IO cycle"
5. Repeat steps 1 to 4 for the ET200SP-R1_2 station.
Result: The R1 devices are connected to the S7-1500H redundant system.
Figure 9-10 R1 devices assigned in the network view with system redundancy

Table of Contents

Other manuals for Siemens Simatic S7-1500

Related product manuals