EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 308

Siemens Simatic S7-1500
523 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
9.7 Configuring the system power supply
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
307
Infeed via the R/H-CPU
Supply the R/H-CPU with the permissible 24 V DC supply voltage.
Follow these steps to set up the infeed via the R/H-CPU:
1. In STEP 7, open the "Properties" tab for the R/H-CPU. Select "System power supply" in the
navigation.
2. Select the option "Connection to supply voltage L+".
Figure 9-12 Supply voltage via R/H-CPU only
Infeed via R/H-CPU and system power supply
Supply the system power supply with the permissible supply voltage and the R/H-CPU with
24 V DC.
Both the system power supply and the R/H-CPU supply current to the backplane bus. The
supplied power is summed.
Power addition: Infeed power of the system power supply + infeed power of the R/H-CPU
Follow these steps to set up the infeed via the R/H-CPU and system power supply:
1. In STEP 7, open the "Properties" tab for the R/H-CPU. Select "System power supply" in the
navigation.
2. Select the option "Connection to supply voltage L+".
Figure 9-13 Supply voltage system via the R/H-CPU and system power supply
Infeed via system power supply only
You can also feed the required power into the backplane bus using only a system power
supply. In this case, the R/H-CPU is supplied from the backplane bus rather than with 24 V DC.
In general, you can use a system power supply with AC or DC infeed for the configuration.