New properties/functions   
 
  S7-1500R/H redundant system 
30  System Manual, 01/2024, A5E41814787-AF 
What's new in the System Manual S7-1500R/H redundant system, edition 11/2022 compared to 
edition 05/2021 
 
 
What's 
  What are the customer benefits?  Where can I find the infor-
tents 
PROFINET system 
redundancy R1 
As of FW version V3.0, the S7-1500H redundant 
system supports PROFINET system redundancy R1: 
•  ET200SP IM 155-6 PN R1 
(6ES7155-6AU00-0HM0) 
•  ET 200SP HA IM 155-6 PN HA 
(6DL1155-6AU00-0PM0) 
•  ET 200iSP IM 152-1 PN (6ES7152-1BA00-0AB0) 
R1 devices are equipped with two interface mod-
ules compared to S2 devices. If one interface mod-
ule fails, the R1 device can still be reached by the H-
CPUs via the second interface module. Thus, R1 
devices have a higher availability than S2 devices. 
As of the System overview 
(Page 63) section 
New configuration 
variants for S7-1500H 
As of FW version V3.0, the S7-1500H redundant 
system supports additional configuration variants:  
•  Configuration of PROFINET rings with R1 devices 
•  Configuration of a line topology with S2 devices, 
switched S1 devices 
•  Configuration of a line topology with R1 devices 
•  Configuration of a combined topology with R1 
devices, S2 devices 
•  Configuration without additional devices 
This allows you to connect the S7-1500H redundant 
system to almost any network topology and solve 
complex automation tasks. 
As of the System overview 
(Page 63) section 
As of FW version V3.0, OB 70 (I/O redundancy error) 
is available for the diagnostics of R1 and S2 devices 
Section Basics of program edit-
ing (Page 317) 
ule up to 40 km 
As of FW version V3.0, a new synchronization mod-
ule Sync Module 1 GB FO 40 km is available. The 
synchronization module enables a spatial distance 
of the two H-CPUs of up to 40 km via optical fibers. 
This allows you to use the S7-1500H redundant 
system for long tunnel installations. 
As of Connecting (Page 273) 
section 
As of FW version V3.0, the instructions for the data 
block functions are supported: 
•  CREATE_DB (create data block) 
•  READ_DBL (Read from data block in the load 
memory) 
•  WRIT_DBL (Write to data block in load memory) 
•  DELETE_DB (delete data block)