Commissioning
12.8 Identification and maintenance data
S7-1500R/H redundant system
430 System Manual, 01/2024, A5E41814787-AF
Table 12- 19 Record structure for I&M identification data
Identification data
Access
Example
Explanation
Identification data 0: (record index AFF0H)
VendorIDHigh
Read (1 bytes)
0000H
Vendor name
(002A
H = SIEMENS AG)
VendorIDLow
Read (1 bytes)
002A
H
Order_ID
Read (20 bytes)
6ES7515-2RM00-0AB0
Article number of module
(for example CPU 1515R-1 PN)
IM_SERIAL_NUMBER
Read (16 bytes)
-
Serial number (device-specific)
IM_HARDWARE_REVISION
Read (2 bytes)
1
corresponds to hardware version
(e.g. 1)
IM_SOFTWARE_REVISION
Read
Firmware version
Provides information about the firmware
version of the module (e.g. V1.0.0)
SWRevisionPrefix
(1 byte)
V
IM_SWRevision_Functional_E
nhancement
(1 byte)
0000
H
- 00FF
H
IM_SWRevision_Bug_Fix
(1 byte)
0000
H
- 00FF
H
IM_SWRevision_Internal_
Change
(1 byte)
0000
H
- 00FF
H
IM_REVISION_COUNTER
Read (2 bytes)
0000
H
Provides information about parameter
changes on the module
(not used)
IM_PROFILE_ID
Read (2 bytes)
0000 H
Generic Device
IM_PROFILE_SPECIFIC_TYPE Read (2 bytes)
0001H
CPU
0003
H
I/O modules
IM_VERSION
Read
0101
H
Provides information on the ID data ver-
sion
(0101
H = Version 1.1)
IM_Version_Major
(1 byte)
IM_Version_Minor
(1 byte)
IM_SUPPORTED Read (2 bytes) 000EH provides information about the available
identification and maintenance data
(I&M1 to I&M3)
Maintenance data 1: (Record index AFF1H)
IM_TAG_FUNCTION
Read/write (32
bytes)
-
Enter an identifier for the module here,
that is unique plant-wide.
IM_TAG_LOCATION
Read/write (22
bytes)
-
Enter the installation location of the
module here.
Maintenance data 2: (Record index AFF2H)
IM_DATE Read/write (16
bytes)
YYYY-MM-DD HH:MM Enter the installation date of the module
here.
Maintenance data 3: (Record index AFF3H)
IM_DESCRIPTOR
Read/write (54
bytes)
-
Enter a comment about the module here.

Table of Contents