EasyManua.ls Logo

Siemens SIMATIC S7-400H - Process for Update

Siemens SIMATIC S7-400H
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Linking and Synchronizing
6-5
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
RUN
Status message “Synchronize” to
all partners logged on
Update(REDF LEDs flash at 2 Hz)
STOP
Master copies outputs
Master copies timers, counters, markers,<inputs and the dia-
gnostics buffer
Master CPU (CPU 0)
Standby CPU
(CPU 1))
Asynchronous SFCs for data records
<given negative acknowledgement
*)
Messages delayed
All OBs up to priority class 15 (incl. OB
1) delayed
Start of monitoring for max.<scan-cycle
time extension
Start of monitoring for max. communica-
tion delay
Start of monitoring for max. blockage
time for priority classes > 15
Current comm. jobs <delayed or new
ones rejected
OBs of priority classes > 15 are delayed
with the exception of the watchdog in-
terrupt OB with special treatment
*)
A detailed description of the SFCs, SFBs and communication functions concerned can be
found in the sections below
If appropriate, execution of watchdog
interrupt OB with special treatment
Start of min. I/O retention time
Master copies the contents of the data blocks <that have been
modified since they were last copied
Master copies contents of the modified data blocks
Master role
change
Figure 6-2 Process for update