EasyManua.ls Logo

Siemens SIMATIC S7-400H - Availability

Siemens SIMATIC S7-400H
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Characteristic Values of Redundant Programmable Logic Controllers
A-3
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
Availability
Availability is the probability of a system being capable of operation at a specified
point of time. It can be enhanced by means of redundancy – for example, by using
redundant I/O modules or by using multiple sensors at one sampling point.
Redundant components are arranged such that system operability is not affected
by the failure of a single component. Here, again, an important element of
availability is a detailed diagnostics display.
The availability of a system is expressed as a percentage. It is determined by the
mean time between failure (MTBF) and the mean repair time (MTTR). The
availability of a two-channel (2-out-of-2) fault-tolerant system can be calculated
from the following formula:
V +
MTBF
1v2
MTBF
1v2
) MDT
100%