Using I/O on the S7-400H
7-28
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
Redundant analog input module for direct current measurements
The following applies to the analog input module circuit shown in the diagram
above:
Suitable encoder types are: Active 4-wire and passive 2-wire measurement
transducers with an output range of +/–20 mA, 0...20 mA and 4...20 mA. 2-wire
measurement transducers are connected to an external auxiliary voltage.
The “wire break” diagnostic function supports only the input range 4...20 mA. All
other unipolar or bipolar ranges are not supported.
Suitable diodes: The BZX85 or 1N47..A (Zener diodes 1.3W) series, of the
voltage range specified in the module data. For the selection of other elements
you should note that the off-state forward current is as low as possible.
In this type of circuit and when using the named diodes, a principal
measurement error is caused by the off-state forward current of maximum 1A.
In the 20-mA range with 16-bit resolution, this value results in an error < 2 bits.
In the circuit above, various analog inputs return an additional error. For further
information, refer to the marginal conditions. These and all other error values
specified in the module manual form a cumulative error.
The 4-wire measurement transducers used must be capable of driving the load
of the above circuit. For further information, refer to the marginal conditions.
Please note that the installation of a Zener diode circuit forms a heavy influence
on the voltage requirements of 2-wire measurement transducers, which is why
the necessary input voltages are specified in the technical data of the various
modules. The internal supply (
IS
) of the measurement transducer (
MT
)
determines the minimum supply voltage and is calculated as follows:
L+ > Uin–2Dr + UIS–MT
This module is not suitable for the use in the circuit shown above:
AI 8x12bit 6ES7 331-7KF02-0AB0