Failure and Replacement of Components During Operation
10-15
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
10.2.3 Failure and Replacement of a PROFIBUS-DP Slave
Initial situation
Failure How Does the System React?
The S7-400H is in redundant system mode
and one DP slave fails.
Both CPUs report the event in the
diagnostics buffer and via the appropriate
OB.
Procedure
To replace a DP slave, perform the following steps:
Step What Has To Be Done? How Does the System React?
1 Turn off the supply for the DP slave. -
2 Unplug the connected bus connector. -
3 Replace the DP slave. -
4 Plug the bus connector on and turn the
supply back on.
CPUs process the mounting rack
failure OB 86 in synchronism
(outgoing event).
DP slave can be addressed by the
relevant DP master system.