Linking and Synchronizing
6-18
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
Monitoring time accuracy
Note
The monitoring times determined by STEP7 or by using the formulas merely
represent a recommendation.
They are based on a fault-tolerant system with two communication peers and an
average communication load.
Since your system profile may vary sharply from this assumption, you must take
note of the following rules.
The rise in scan cycle time can increase sharply at a high communication load.
If you perform changes to your system while it is operating, the rise in scan
cycle time can increase appreciably as a result.
The more program scanning (especially processing of communication blocks)
you perform in priority classes > 15, the higher the communication delay and
scan cycle time delay might grow.
You can even undercut the calculated monitoring times in small systems with
high performance requirements.
Use of redundant input and output modules
Notice
If you have redundant I/O modules and have taken this into account in your
program accordingly, you might have to add a premium to the calculated
monitoring times, so that surging does not occur at the output modules.
A premium is required only if you operate modules redundantly from the following
table.