Synchronization Module
12-5
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
Changing the Operating Mode of an H CPU
To change the operating mode of an H CPU, carry out one of following procedures
depending on the operating mode you wish to change to and the module rack
number of the CPU:
Changing from redundant to single mode
1. Remove the interface module.
2. Perform a power on without backup e.g., by removing and inserting the CPU.
3. Load a project into the CPU in which it is configured for single mode.
Changing from Single to Redundant Mode, Module Rack Number 0
1. Connect the synchronization modules set for rack number 0.
2. Perform a power on without backup e.g., by removing and inserting the CPU.
3. Load a project into the CPU in which it is configured for redundant mode.
Changing from single to redundant mode, module rack number 1
1. Connect the synchronization modules set for rack number 1.
2. Perform a power on without backup e.g., by removing and inserting the CPU.
3. Load a project into the CPU in which it is configured for redundant mode.
Cable length up to 500m
You can use the synchronization module in 2 pairs with fiber optic cables of up to
500m as of product release 2 .
S7-400 with CPU 417-4H
rack 1
S7-400 with CPU 417-4H
rack 0
SC/ST
Splicebox
SC/ST
Splicebox
Prefabricated
cable
Prefabricated
cable
max. 500m
The following points are important:
You can use the synchronization modules with product release 1 and 2 together
and this will make a cable length of up to 10m possible.
Make sure there is enough strain relief on the modules if you use fiber optic
cables longer than 10m.
Adhere to the specified ambient conditions for using fiber optic cables (bending
radius, pressure, temperature...)
Note the technical specifications of the fiber optic cable (attenuation,
bandwidth...)