Technical Specifications
13-2
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
13.1 Technical Specifications of the CPU 414-4H;
(6ES7 414-4HJ00-0AB0)
CPU and Version
MLFB
Hardware version
6ES7 414-4HJ00-0AB0
01
Firmware version 3.1 V
Associated programming
package
beginning with STEP7 V
5.2;
optional package
S7 H System
Memory
Working memory
Integrated 384 Kbytes for code
384 Kbytes for data
Expandable No
Load memory
Integrated 256 Kbytes RAM
Expandable FEPROM With memory card (FLASH)
up to 64 Mbytes
Expandable RAM With memory card (RAM)
up to 64 Mbytes
Backup Yes
With battery All data
Without battery None
Processing Times
Processing times for
Bit operations Min. 0.1 s
Word instructions Min. 0.1 s
Integer math
instructions
Min. 0.1 s
Floating-point math
instructions
Min. 0.6 s
Timers/Counters and Their Retentivity
S7 counters 256
Retentivity can be set From Z 0 to Z 255
Preset From Z 0 to Z 7
Counting range 1 to 999
IEC counter Yes
Type SFB
S7 timers 256
Retentivity can be set From T 0 to T 255
Preset No retentive timers
Time range 10 ms to 9990 s
IEC timers Yes
Type
SFB
Data Areas and Their Retentivity
Total retentive data area
(incl. memory markers,
timers, counters)
Total working and load
memory (with backup
battery)
Memory markers 8 Kbytes
Retentivity can be set From MB 0 to MB 8191
Preset retentivity From MB 0 to MB 15
Clock memories 8 (1 memory byte)
Data blocks Max. 4095 (DB 0 reserved)
Size Max. 64 Kbytes
Local data (can be set) Max. 16 Kbytes
Preset 8 Kbytes
Blocks
OBs See instruction list
Size Max. 64 Kbytes
Nesting depth
Per priority class 24
Additionally in an error
OB
2
FBs Max. 2048
Size Max. 64 Kbytes
FCs Max. 2048
Size Max. 64 Kbytes
Address Areas (Inputs/Outputs)
Total I/O address area 8 Kbytes/8 Kbytes
Of which distributed
MPI/DP interface 2 Kbytes/2 Kbytes
DP interface 6 Kbytes/6 Kbytes
Process Image 8 Kbytes/8 Kbytes
(can be set)
Preset 256 bytes/256 bytes
Number of partial
process images
Max. 8
Consistent data Max. 244 bytes
Digital channels 65536/65536
those central 65536/65536
Analog channels 4096/4096
those central 4096/4096

Table of Contents