EasyManua.ls Logo

Siemens SIMATIC S7-400H - Page 125

Siemens SIMATIC S7-400H
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Linking and Synchronizing
6-23
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
5. From formula [1]:
T
P15
(DP master system_1)
= 1250 ms – (2 × 25 ms + 300 ms + 50 ms + 100 ms + 30 ms) = 720 ms
T
P15
(DP master system_2)
= 1200 ms – (2 × 30 ms + 300 ms + 50 ms + 80 ms + 50 ms) = 660 ms
Check: if T
P15
> 0, continue with
6. T
P15_HW
= MIN (720 ms, 660 ms) = 660 ms
7. From formula [2]:
T
P15_OD
= 50 ms + T
PH
= 50 ms + 90 ms = 140 ms
Check: if T
P15_OD
= 140 ms < T
P15_HW
= 660 ms, continue with
8. From Section 6.3.4 for 170 Kbytes user program data:
T
P15_AWP
= 194 ms
Check: if T
P15_AWP
= 194 ms < T
P15_HW
= 660 ms, continue with
9. Formula [3] now provides the recomm. max. blocking time for priority classes
> 15:
T
P15
= MAX (194 ms, 140 ms)
T
P15
= 194 ms
Entering 194 ms for the maximum blocking time for priority class > 15 in STEP 7
ensures that a signal change during the update will always be recognized when the
signal lasts 1250 ms or 1200 ms.
Remedies if it is not possible to calculate T
P15
If no recommendation results from the calculation of the maximum blocking time
for priority classes > 15, you can remedy this by various measures:
Reduce the watchdog interrupt cycle of the watchdog interrupt configured.
For particularly high T
TR
times, divide the slaves into several DP master
systems.
Increase the transmission rate on DP master systems affected.
Configure the DP/PA links and Y links in separate DP master systems.
If the DP slaves have very different switch-over times and thus (generally) great
variations in T
PTO
, distribute these slaves among a number of DP master
systems.
If only a small load due to interrupts or parameter assignment is to be expected
in the individual DP master systems you can also reduce the T
TR
times
calculated by approx. 20–30%. This will increase the risk of a station failure
occurring in the distributed I/O.

Table of Contents

Other manuals for Siemens SIMATIC S7-400H

Related product manuals