Failure and Replacement of Components During Operation
10-10
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
Initial situation
Failure How Does the System React?
Simultaneous Failure of a Fiber–Optic or
Synchronization Module:
The S7-400H is in redundant system mode
and both fiber-optic cables or
synchronization submodules fail.
Both CPUs report the event in the
diagnostics buffer and via OB 72.
Both CPUs become the master CPU and
remain in RUN mode.
Procedure
The double error described results in loss of redundancy. In this event proceed as
follows:
Step What Has To Be Done? How Does the System React?
1 Switch off a subsystem. -
2 Replace the faulty components. -
3 Turn the subsystem back on. LEDs IFM1F and IFMF2F go out. The
standby LED lights.
4 Start the CPU (e.g. STOP³RUN or
Start via programming device).
CPU performs automatic LINK-UP
and UPDATE.
CPU changes to RUN (Redundant
system mode) and now operates
as the standby CPU.