Technical Specifications
13-6
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
13.2 Technical Specifications of the CPU 417-4H;
(6ES7 417-4HL01-0AB0)
CPU and Version
MLFB
Hardware version
6ES7 417-4HL01-0AB0
01
Firmware version 3.1 V
Associated programming
package
beginning with STEP7 V
5.2;
optional package
S7 H System
Memory
Working memory
Integrated 2 Mbytes for code2 Mbytes
for data
Expandable Up to 10 Mbytes for
codeUp to 10 Mbytes for
data
Load memory
Integrated 256 Kbytes RAM
Expandable FEPROM With memory card (FLASH)
up to 64 Mbytes
Expandable RAM With memory card (RAM)
up to 64 Mbytes
Backup Yes
With battery All data
Without battery None
Processing Times
Processing times for
Bit operations Min. 0.1 s
Word instructions Min. 0.1 s
Integer math
instructions
Min. 0.1 s
Floating-point math
instructions
Min. 0.6 s
Timers/Counters and Their Retentivity
S7 counters 512
Retentivity can be set From Z 0 to Z 511
Preset From Z 0 to Z 7
Counting range 1 to 999
IEC counter Yes
Type SFB
S7 timers 512
Retentivity can be set From T 0 to T 511
Preset No retentive timers
Time range 10 ms to 9990 s
IEC timers Yes
Type
SFB
Data Areas and Their Retentivity
Total retentive data area
(incl. memory markers,
timers, counters)
Total working and load
memory (with backup
battery)
Memory markers 16 Kbytes
Retentivity can be set From MB 0 to MB 16383
Preset retentivity From MB 0 to MB 15
Clock memories 8 (1 memory byte)
Data blocks Max. 8191 (DB 0 reserved)
Size Max. 64 Kbytes
Local data (can be set) Max. 64 Kbytes
Preset 32 Kbytes
Blocks
OBs See instruction list
Size Max. 64 Kbytes
Nesting depth
Per priority class 24
Additionally in an error
OB
2
FBs Max. 6144
Size Max. 64 Kbytes
FCs Max. 6144
Size Max. 64 Kbytes
Address Areas (Inputs/Outputs)
Total I/O address area 16 Kbytes/16 Kbytes
Of which distributed
MPI/DP interface 2 Kbytes/2 Kbytes
DP interface 8 Kbytes/8 Kbytes
Process Image 16 Kbytes/16 Kbytes
(can be set)
Preset 1024 bytes/1024 bytes
Number of partial
process images
Max. 8
Consistent data Max. 244 bytes
Digital channels 131072/131072
those central 131072/131072
Analog channels 8192/8192
those central 8192/8192