Technical Specifications
13-9
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
3rd Interface
Type of interface Plug-in interface submodule
(fiber-optic cable)
Insertable interface
submodule
Synchronization module
IF 960 (only during
redundancy mode; during
single mode the interface is
free/covered)
4th Interface
Type of interface Plug-in interface submodule
(fiber-optic cable)
Insertable interface
submodule
Synchronization module
IF 960 (only during
redundancy mode; during
single mode the interface is
free/covered)
Programming
Programming language LAD, FBD, STL, SCL
Instruction set See instruction list
Bracket levels 8
System functions (SFC) See instruction list
Number of SFCs active at
the same time
• WR_REC 8
• WR_PARM 8
• PARM_MOD 1
• WR_DPARM 2
• DPNRM_DG 8
• RDSYSST 1 ... 8
System function blocks
(SFB)
See instruction list
Number of SFCs active at
the same time
• RD_REC 8
• WR_REC 8
User program protection Password protection
Access to consistent data
in the process image
Yes
Dimensions
Mounting dimensions
B×H×T (mm)
50×290×219
Slots required 2
Weight Approx. 1.07 kg
Voltages, Currents
Current consumption from
S7-400 bus (5 VDC)
Typ. 1.8 A
Max. 2.0 A
Current consumption from
the S7-400 bus (24 VDC)
The CPU does not
consume any current at 24
V, and it only makes this
voltage available at the
MPI/DP interface.
Total current consumption
of the components
connected to the MPI/DP
interfaces, with a maximum
of 150 mA per interface
Backup current Typically 75 A
Maximum 860 A
Incoming supply of external
backup voltage to the CPU
5 VDC to 15 VDC
Power loss Typ. 9 W
CPU as DP Slave
You must not configure the CPU as DP slave.