EasyManuals Logo

Siemens SIMATIC S7 F User Manual

Siemens SIMATIC S7 F
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #209 background imageLoading...
Page #209 background image
Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-21
Error in the Case of Module Redundancy
In the event of an error, a switch is made to the analog value of the redundant
module. After the error is corrected, there is no switch back; instead, work
continues with the last valid analog value. If an error only occurs on one of the
redundant modules, automatic reintegration takes place in the F channel driver
F_CH_AI after the error is corrected.
Report Characteristics
The block has no reporting behavior.
See Also
Common Features of the Driver Blocks
Passivation and Reintegration

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 F and is the answer not in the manual?

Siemens SIMATIC S7 F Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7 F
CategoryController
LanguageEnglish

Related product manuals