Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-21
Error in the Case of Module Redundancy
In the event of an error, a switch is made to the analog value of the redundant
module. After the error is corrected, there is no switch back; instead, work
continues with the last valid analog value. If an error only occurs on one of the
redundant modules, automatic reintegration takes place in the F channel driver
F_CH_AI after the error is corrected.
Report Characteristics
The block has no reporting behavior.
See Also
Common Features of the Driver Blocks