EasyManua.ls Logo

Siemens SIMATIC TDC - SM500 Status and fault displays

Siemens SIMATIC TDC
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Signal modules
5.1 SM500 signal module
SIMATIC TDC hardware
System Manual, 08/2017, A5E01114865-AL
105
5.1.3
Status and fault displays
Status displays for SM500
Table 5- 2 Status displays for signal module SM500
LED display
Module status
H1
H2
Off
Off
During voltage run-up
Off
On
FPGAs are configured, module is not initialized
On Off Module is initialized and operating error-free
On On After 3.3 V voltage failure
Hardware failure => Power-down the rack and replace the SM500
5.1.4
Application notes and immunity to interference
Fan operation is required
Interference-proof operation is only possible if the SM500 is firmly attached to the rack.
Insert the module and then bolt it onto the rack accordingly (two screw heads, see
Control and display elements (Page 103)).
The module may not be inserted or removed while the rack is on live voltage.
Note
For more information on fan operation, refer to chapter "
Rack (Page 39)"!
For more information on EMC and environmental c
onditions, refer to chapter "General
technical specifications
(Page 37)"!
Aotewell Ltd
www.aotewell.com
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Related product manuals