Rack
3.2 Rack UR5213 (6DD1682-0CH2)
SIMATIC TDC hardware
System Manual, 08/2017, A5E01114865-AL
57
3.2.6
Wiring diagram
X2
Pin
Function
Screw terminal with screw lock (3*1.5 mm
2
, stranded
wires dressed with wire end ferrules with insulating
collars)
Make sure that the strain relief is properly mounted.
L
Line conductor
N Neutral conductor
PE/ground conductor
X1
Pin
Function
Cage clamp terminal (0.5 mm
2
1.5 mm
2
, stranded
wires dressed with wire end ferrules with insulating
collars)
Make sure that the strain relief is properly mounted.
1, 2
SYSFAIL signaling contact
NC contact
3, 4
POWER signaling contact
NO contact
5, 6
FAN FAIL signaling contact
NO contact
WARNING
The
PE/ground conductor
must be connected to the power supply. A PE/ground terminal
on the rack is inappropriate. The PE/ground conductor must be green with yellow stripe
(green/yellow).
Ungrounded installation of the rack is not planned.